Stainless steel fully enclosed housing with excellent waterproofing and corrosion resistance.
Remote transmission of gas density signals.
Local display of temperature, pressure, and density.
Imported temperature-sensitive components with high accuracy and stable compensation.
Oil-free design, superior vibration and shock resistance.
High-precision contact mechanism using imported components.
RS-485 signal transmission for long-distance communication.
1. Measurement Range:
Relative pressure: -0.1-0.9 MPa; Absolute pressure: 0-1.0 MPa
2. Temperature Accuracy:
0-50°C: ±0.5°C; -40-80°C: ±1.0°C
3. Pressure Accuracy:
0-50°C: ±0.25%
-40-60°C: ±1.0%
4. Density Accuracy:
0-50°C: ±0.5%
-40-60°C: ±1.0%
5. Protection Rating: IP65
6. Sealing Performance: ≤1.0×10?Pa·m³/s
7. Communication Protocol:
Modbus-RTU, Modbus-TCP
8. Operating Temperature: -40°C to +65°C
9. Humidity: ≤95% RH
10. Current Consumption: ≤500 mA
11. Power Supply: 24 VDC (±10%)